CSC-306 generator protection provides comprehensive protection for medium and large generators, including large steam and combustion turbines, combines-cycle generators and hydro units. CSC-306 includes advanced automation and communication capabilities, extensive analog quantity and I/O options.
Generator stator current differential protection, 100% stator and field winding ground fault protection, overexcitation, loss of excitation, unbalance protection and breaker failure protection
Reverse power, Low forword power, power swing blocking and out-of-step tripping, thermal overload protection, phase overcurrent and earth overcurrent protection, under/ over-frequency, under/ over-voltage protection, 5 BIs for non-electric protection
Current differential protection, overcurrent, overload protection of the exciting transformer
Wide range of supported protocols IEC 61850, IEC 60870-5-103, DNP3.0 and Modbus. And redundant communications with zero downtime using PRP protocol
Robust hardware with excellent EMC performance and IP54 protection under -40℃ to 70℃ operating temperature